Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM00657
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/16/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/16/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 04/17/2009 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Approved | |
| 04/20/2009 | GERRY KOZIOL | WWM | REVIEW | Denied | need credit evaluation from 3rd floor |
| 04/21/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The IRC is not the controlling code for this activity; use the 2006 IECC. For the purposes of the 2006 International Energy Conservation Code, R-2 buildings shall comply with the residential energy efficiency requirements (chapter 4). Reference: Section 202, IECC 2006. Note also that there are no Tables N1103.1 or N1103.5 in the 2006 IRC. 2. The duct insulation notes are ambiguous; see Section 403.2, IRC 2006. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 403.2, IECC 2006. 3. Show the R-value of the foam on the drawing. Specify the minimum resistance (R-value) of the foam insulation to be installed in the roof/ceiling assembly (sheet A-8.1). Reference: Section 402.12, IECC 2006. |
| 04/21/2009 | ROBERT SHERRY | WATER | REVIEW | Denied | On January 3, 2005, Tucson Water adopted a policy that eliminated the use of multiple meters (manifolding). Contact Fred Coy of Tucson Water (837-2220) prior to attempting to design around two manifolded meters. |
| 04/22/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not addressed. Provide fixture descriptions for all plumbing fixtures. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc). Reference: Sections 301.1.1 and 401.1, UPC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/28/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 04/28/2009 | SUE REEVES | REJECT SHELF | Completed |