Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM00657
Parcel: 10705126B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM00657
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/16/2009 DAVE MANN FIRE REVIEW Approved
04/17/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
04/20/2009 GERRY KOZIOL WWM REVIEW Denied need credit evaluation from 3rd floor
04/21/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The IRC is not the controlling code for this activity; use the 2006 IECC. For the purposes of the 2006 International Energy Conservation Code, R-2 buildings shall comply with the residential energy efficiency requirements (chapter 4). Reference: Section 202, IECC 2006. Note also that there are no Tables N1103.1 or N1103.5 in the 2006 IRC.
2. The duct insulation notes are ambiguous; see Section 403.2, IRC 2006. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 403.2, IECC 2006.
3. Show the R-value of the foam on the drawing. Specify the minimum resistance (R-value) of the foam insulation to be installed in the roof/ceiling assembly (sheet A-8.1). Reference: Section 402.12, IECC 2006.
04/21/2009 ROBERT SHERRY WATER REVIEW Denied On January 3, 2005, Tucson Water adopted a policy that eliminated the use of multiple meters (manifolding). Contact Fred Coy of Tucson Water (837-2220) prior to attempting to design around two manifolded meters.
04/22/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not addressed. Provide fixture descriptions for all plumbing fixtures. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc). Reference: Sections 301.1.1 and 401.1, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/28/2009 DELMA ROBEY OUT TO CUSTOMER Completed
04/28/2009 SUE REEVES REJECT SHELF Completed