Permit Number: T09CM00619
Parcel: 108170040

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T09CM00619
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2009 DAVE MANN FIRE REVIEW Approved
03/20/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/24/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE INFORMATION ON THE NEW SCREEN WALL. IF THE WALL IS OVER 6' IN HEIGHT, STRUCTURAL CALCULATIONS AND DETAILS ARE REQUIRED.
2. SHEET E-2; ELECTRICAL 1-LINE DIAGRAM: A NOTE AT THE NEW GENERATOR INDICATES A CONCRETE PAD SUPPORT WITH A STRUCTURAL ENGINEERS CALCULATIONS. PROVIDE CALCULATIONS AND DETAILS AT THE NEW PAD.
04/08/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information to show that the installation of the emergency generator complies with the requirements of NFPA 37, particularly chapters 4 and 5. Reference: Section 915, IMC 2006
04/08/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The 2-1/2" header for the existing gas meter is too small per Table 12-8, UPC 2006 for a flow of 1779 CFH at 150 feet of developed length. Size natural gas pipe per Section 1217.1, UPC 2006 or provide calculations demonstrating conformance to Section 1217.3, UPC 2006.
04/14/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/06/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
05/06/2009 SUE REEVES REJECT SHELF Completed