Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T09CM00619
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/20/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 03/20/2009 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/24/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE INFORMATION ON THE NEW SCREEN WALL. IF THE WALL IS OVER 6' IN HEIGHT, STRUCTURAL CALCULATIONS AND DETAILS ARE REQUIRED. 2. SHEET E-2; ELECTRICAL 1-LINE DIAGRAM: A NOTE AT THE NEW GENERATOR INDICATES A CONCRETE PAD SUPPORT WITH A STRUCTURAL ENGINEERS CALCULATIONS. PROVIDE CALCULATIONS AND DETAILS AT THE NEW PAD. |
| 04/08/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide information to show that the installation of the emergency generator complies with the requirements of NFPA 37, particularly chapters 4 and 5. Reference: Section 915, IMC 2006 |
| 04/08/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The 2-1/2" header for the existing gas meter is too small per Table 12-8, UPC 2006 for a flow of 1779 CFH at 150 feet of developed length. Size natural gas pipe per Section 1217.1, UPC 2006 or provide calculations demonstrating conformance to Section 1217.3, UPC 2006. |
| 04/14/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/06/2009 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 05/06/2009 | SUE REEVES | REJECT SHELF | Completed |