Review Date Reviewer's Name Type of Review Description Status Comments
03/25/2009 GERRY KOZIOL WWM REVIEW Approved
04/14/2009 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 4-15-09
Activity: T09CM00609
Address: 1635 E 8th St.
Applicant: Phil Brueggemann

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

SITE PLAN:
2. Provide keynotes for keynote references on site plan.

ELEVATIONS:
3. Specify two-layer underlayment for low-slope shingle roofs (2:12 to 4:12), R905.2.7.
4. Unvented roof design specified does not include shingle roof coverings.

SECTIONS - DETAILS:
5. Holdown hardware specified does not provide the minimum uplift capacity for alternate braced wall panels,

PLUMBING PLAN:
6. All SFR and Duplex plans submitted after March 1, 2009 require a solar water system, or future installation preparation with one of the following provisions: control and ¾"water piping; 3" metallic sleeve; or an accessible attic over the water heater.
7. Buildings shall be individually metered for each dwelling unit, IPC 301.4.1. Provide a separate water meter for the proposed unit.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review