Permit Number: T09CM00586
Parcel: 13101023B

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T09CM00586
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2009 DAVE MANN FIRE REVIEW Denied Please include the following fire sprinkler design criteria to the plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 791-3234
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards.
4. The density required of the water supply.
03/16/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/18/2009 JASON GREEN ENGINEERING REVIEW Denied DATE: March 18, 2009
REVIEWERS: Jason Green, CFM
ACTIVITY: T09CM00586 (Building Plan)


SUMMARY: Engineering Division of Development Services Department has received the building plan (T09CM00586) for the above referenced property. Engineering Division does not recommend approval of the building plan application at this time. The following items need to be addressed:


BUILDING PLAN COMMENTS:

Engineering cannot approve the building plan until approval of the proposed Development Plan D08-0047. Provide a copy of the approved Development Plan with the next building plan submittal.

Engineering will re-review the building plan on the next submittal to insure compliance with the approved Development Plan. Additional comments may be forthcoming.


GENERAL COMMENTS:

Further comments may be generated upon re-submittal of the building plan review.

For questions or to schedule an appointment I can be reached at 837-4929.




Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services
03/19/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SEE BUILDING COMMENTS ON PROJECT T09CM00583.
03/20/2009 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 1884 S. Craycroft Rd
T09CM00583 & T09CM00586
Building Plan (1st Review)

TRANSMITTAL DATE: March 20, 2009

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development package. Please submit two copies of the approved and stamped development, package with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped development plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t09cm00583.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
03/24/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The minimum opening height for a scupper is 4". Reference: Section 1101.11.2.1, UPC 2006.
03/24/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/31/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
03/31/2009 SUE REEVES REJECT SHELF Completed