Permit Number: T09CM00574
Parcel: 99999999M

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T09CM00574
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2009 MARTIN BROWN FIRE REVIEW Denied Provide no parking signs on roads in areas required by IFC Appendix D as amended.

Provide fire knox box for gates. Key for responding department.
03/19/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/03/2009 BIANCA RAMIREZ ENGINEERING REVIEW Denied Unable to approve building plan until the comments from grading plan: T09BU00361 have been addressed. Changes to grading plan could potentially affect the design of the building plans for construction of the road.

Submittal for light poles and reconstruction of existing road cannot be approved until floodplain limits have been identified. Reference grading comments.


Bianca Ramirez, CFM
Engineering Associate
520-837-4928
04/14/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/16/2009 CPIERCE1 OUT TO CUSTOMER Completed
04/16/2009 SUE REEVES REJECT SHELF Completed