Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/12/2009 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
03/13/2009 | MARTIN BROWN | FIRE | REVIEW | Approved | |
03/17/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. ALL DEFERRED SUBMITTALS MUST BE APPROVED BY THE BUILDING OFFICIAL, JESSIE SANDERS. 2. INCLUDE CODE ANALYSIS DATA ON THE DRAWINGS PER IBC SECTION 106.1.1. INFORMATION SHOULD INCLUDE OCCUPANCY GROUP, OCCUPANCY LOAD, EXIT REQUIREMENTS, ACCESSIBILITY REQUIREMENTS, PLUMBING REQUIREMENTS, HOW THE NEW OCCUPANCY LOAD AFFECTS EXISTING CONDITIONS, ETC. 3. SHEET A1; FOUNDATION PLAN: THE ACCESSIBLE TURNING CIRCLE SHOWN ON THE PLAN INDICATES THAT THE RESTROOMS ARE ACCESSIBLE. WHY ARE THESE INDICATED ON THIS PROJECT? 4. SHEET A1; SHEAR WALL/HOLDOWN SCHEDULES: ENLARGE THE PRINT TO A MINIMUM OF 3/32" FOR CLARITY. 5. SHEET A3; ROOF FRAMING PLAN: PROVIDE DETAILS FOR THE NEW ROOF TRUSSES OVER THE EXISTING ROOF FRAMING. INDICATE NEW FRAMING AND CONNECTIONS AT THE OVERFRAMING. 6. SHEET A3; ROOF FRAMING PLAN: PROVIDE A DETAIL TO BRACE AND SUPPORT THE TOP OF THE NEW INTERIOR, NON BEARING WALLS TO RESIST LATERAL FORCES REQUIRED BY IBC SECTION 1607.13. 7. SHEET A3; ROOF FRAMING PLAN: ADD LINTEL DESIGNATION L-1 TO NEW OPENING IN EXISTING WALL. 8. SHEET MP1; MECHANICAL FLOOR PLAN: PROVIDE DESIGN AND DETAILS OF THE WALL AND WALL FOUNDATION AT THE CONDENSING UNITS. |
03/25/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
03/26/2009 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
03/26/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide energy code compliance calculations for the building envelope. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006. 2. Show how the fan coil is being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006. 3. Show how adequate access is being provided for the equipment located in the attic space. Reference:: Section 306.3, IMC 2006. 4. Clarify the termination points for the relocated and the new condensate drains. Condensate drains that terminate to the outside shall not cause any surface runoff. (Note that keynote #9 does not seem to appear on the mechanical floor plan.) Reference: Section 307.2.1, IMC 2006, as amended by the City of Tucson. |
03/26/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
03/31/2009 | TERRY STEVENS | ZONING | REVIEW | Denied | 03/31/2009 Development Services Department Zoning Review Section Terry Stevens Lead Planner Comments: 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming. |
04/09/2009 | PAUL MACHADO | ENGINEERING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/17/2009 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
04/17/2009 | SUE REEVES | REJECT SHELF | Completed |