Permit Number: T09CM00563
Parcel: 11711076A

Address:
126 E ALAMEDA ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM00563
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/30/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/01/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied provide detail showing cooling tower make-up water connection to domestic water. include method of backflow protection. show isolation valve to domestic water and include bypass and quick disconnect for emergency domestic water connection.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/07/2009 SUE REEVES OUT TO CUSTOMER Completed
05/07/2009 SUE REEVES REJECT SHELF Completed