Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T09CM00563
Parcel: 11711076A

Address:
126 E ALAMEDA ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM00563
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2009 RONALD BROWN ADA REVIEW Passed NOT A COT OWNED/OPERATED PROPERTY
03/12/2009 MARTIN BROWN FIRE REVIEW Approved
03/12/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/18/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. THE SPECIAL INSPECTION CERTIFICATE NEEDS TO HAVE THE NAME OF EACH INSPECTOR LISTED FOR EACH CATEGORY OF INSPECTION.
2. ALL DEFERRED SUBMITTALS MUST BE APPROVED BY THE BUILDING OFFICIAL, JESSIE SANDERS.
3. SHEET S1.1; DETAIL 06: INDICATE THE NOTE REFERENCES ON THE DETAIL.
4. SHEET S1.1 (DETAIL 04); CALCULATIONS PAGE 10: DETAIL 04 INDICATES A SINGLE ANGLE 8X4X1/2 OVER THE NEW LOUVER OPENING, WHILE THE CALCULATION OF PAGE 10 INVESTIGATES A DOUBLE ANGLE 8X4X1/2. CLARIFY.
03/18/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
03/30/2009 ROBERT SHERRY WATER REVIEW Approved
03/30/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify how the emergency cross-connection of the domestic water system is to be accomplished, i.e. provide a clearer picture of how the connection is to be made, including the pipe sizes, the type of backflow prevention assembly involved and if the work will affect the fire pump system. Reference: Section 103.2.3, UPC 2006.
03/30/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify which of the two versions of specification section 15180 is being used for this project: "Duct, Pipe & Equipment Insulation" or "Pipe and Equipment Insulation". Reference: Section 104.2, IECC, 2006.
2. Provide the maximum conductivity (k-value) that will be allowed for insulation of the chilled water piping, chilled water pumps, and chilled water equipment. Reference: Section 503.2.8, IECC, 2006.
3. Show how the new fan coil is being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006.
03/31/2009 GERRY KOZIOL WWM REVIEW Approved
04/03/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/09/2009 CPIERCE1 OUT TO CUSTOMER Completed
04/09/2009 SUE REEVES REJECT SHELF Completed