Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM00556
Parcel: 110113620

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM00556
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2009 STEVE SHIELDS ZONING REVIEW Approved
03/11/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
03/12/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/12/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the outside air calculations to include an air distribution effectiveness factor of 0.8 per Table 6-2, ASHRAE 62.1-2004.
2. State the required R-value for the duct insulation. See the local amendments to Section 503.2.7, IECC 2006.
3. Provide a duct smoke detector in the return duct. Reference: Section 606.1, IMC 2006.
03/12/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/12/2009 ROBERT SHERRY WATER REVIEW Approved
03/12/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify the status of the Rockford grease interceptor - the catalog states that an external flow control is not needed but the installation drawing in the same catalog shows an external flow control device installed with a GF series interceptor.
03/12/2009 MARTIN BROWN FIRE REVIEW Approved
03/12/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
03/12/2009 ERIC NEWCOMB ADA REVIEW Passed
03/17/2009 CPIERCE1 WWM REVIEW Needs Review
03/17/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review