Permit Number: T09CM00550
Parcel: 13317062G

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T09CM00550
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2009 MARTIN BROWN FIRE REVIEW Denied Please show location of existing fire hydrant(s) with dimensions to property lines. They must be within 500' (as the hose lays) of all parts of the building.
03/11/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/13/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A0.2; SHEET E5.0 (LIGHT POLE): ARE ALL LIGHT POLES 20' MAXIMUM HEIGHT? IF GREATER, A STRUCTURAL ANALYSIS FOR THE POLE FOUNDATION IS REQUIRED.
2. SHEET A6.2: AS PER THE PLUMBING FIXTURE SPECIFICATION SCHEDULE, THE OVERFLOW ROOF DRAIN (ORD) IS TO HAVE A 2" HIGH DAM. PER DETAIL 12/A6.2, IT APPEARS AS THE DAM IS UPSIDE DOWN. VERIFY.
3. SHEET S103; DETAILS 119 AND 122: THE PARTITION SUPPORT TO AND SUSPENSION FROM ALL STRUCTURAL TJI'S ARE TO HAVE FULL LENGTH (TO TOP AND BOTTOM CHORD) WEB STIFFENERS AS PER THE MANUFACTURER'S RECOMMENDATION. PLEASE NOTE THIS ON THE DRAWING DETAILS.
4. SHEET S300 (ROOF FRAMING PLAN); SHEET S500 (DETAILS 503 AND 504): ARE DETAILS 503 AND 504 REVERSED? CLARIFY.
5. ARCHITECT SHOULD SEAL, SIGN, AND DATE THE SPECIFICATIONS. REMOVE ITEMS LISTED IN THE SPECIFICATIONS THAT ARE NOT PERTINENT TO THIS PROJECT.
03/16/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
03/19/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/23/2009 STEVE SHIELDS ZONING REVIEW Approved
03/26/2009 GERRY KOZIOL WWM REVIEW Approved
04/02/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Note: Plumbing review for the shell building limited to roof drain piping, piping at the roof structure or in the walls, and piping below the slab.

1. Provide the civil plans called out on sheet A0.2 that show the work to be done on the water service and building sewer piping. Note that sheet A0.2 appears to show a backflow preventer for the irrigation piping but not for the building water service and no connection to the public sewer is shown.
2. Clarify how locating the shutoff valve for the water service to the building in the fire riser room complies with the accessibility requirements of Section 605.2, UPC 2006.
3. Show the slope of the horizontal rainwater pipes located along column line 7 on the plans. Confirm that the pipe capacity conforms to the requirements of Table 11-2. Reference: Section 1106.2, UPC 2006.
04/03/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the energy compliance statement on sheet M9.1 to correspond to the building shown on the drawings. Approximately half of the windows have a projection factor much less than 0.25, not greater than 0.50 as noted. The architectural drawings and specifications have conflicting descriptions of the fenestration types, none of which seems to be "all other".
04/03/2009 ROBERT SHERRY WATER REVIEW Denied Provide the civil plans called out on sheet A0.2 that show the work to be done on the water service piping. Note that sheet A0.2 appears to show a backflow preventer for the irrigation piping but not for the building water service.
04/06/2009 LOREN MAKUS ENGINEERING REVIEW Approved
04/13/2009 JEFF DRUMM LANDFILL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/14/2009 CPIERCE1 OUT TO CUSTOMER Completed