Permit Number: T09CM00545
Parcel: 123172730

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM00545
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2009 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 3-20-09
Activity: T09CM00545
Address: 1309 E. Lee St.
Applicant: Carolyn Lemmon

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

PLUMBING PLAN:
2. Provide vent piping through the roof so that the aggregate cross-sectional area shall not be less than that of the largest required building sewer, UPC 904.1. (Although a note is present on the plan regarding this requirement, the vent sizing specified does not comply)
3. Provide note requiring that water hammer arrestors be installed in accordance with ASSE 1010-2004 on water lines serving appliances equipped with quick-closing valves to include but not limited to: clothes washers, dishwashers, and refrigerators, UPC 609.10.
4. All SFR and Duplex plans submitted after March 1, 2009 require a solar water system, or future installation preparation with one of the following provisions: control and ¾"water piping; 3" metallic sleeve; or an accessible attic over the water heater.

ELECTRICAL PLAN:
5. Receptacles shall not be located below a counter where the countertop extends more than 6" beyond its support base, E3801.4.5

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review