Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM00544
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/10/2009 | TERRY STEVENS | ZONING | REVIEW | Approved | |
03/10/2009 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
03/11/2009 | RONALD BROWN | ZONING HC SITE | REVIEW | Approved | |
03/11/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
03/11/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/11/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/11/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the waste and vent design to show the traps, vents for the plumbing fixtures. 2. Revise the design for the hydromechanical grease interceptor. 3. Coordinate the water piping sizes. 4. Provide maximum of 110 degree water to the public lavatories. 5. Provide calculations for the water heater support. |
03/11/2009 | MARTIN BROWN | FIRE | REVIEW | Approved | |
03/11/2009 | RONALD BROWN | ADA | REVIEW | Passed | NOT A COT OWNED/OPERATED PROPERTY |
03/30/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
03/30/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
03/30/2009 | CAGUILA1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |