Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. A dual-check valve is not approved for use with a carbonated beverage dispenser. Reference: Section 603.4.12 and Table 6-2 (high hazard, back-siphonage, back-pressure), UPC 2006.
2. Provide a copy of the approved petition of appeal to the building official that allows multiple users for the gravity grease interceptor. Reference: Sections 306.1 and 1014.3.4.3, UPC 2006.