Permit Number: T09CM00539
Parcel: 105110630

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM00539
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the plumbing plan (1/P1), the waste and vent diagram (detail 1/P3), and the plumbing schedule (P4): fixtures P-6 and 10 are shown variously with a 2" waste and a 3" waste. Reference: Section 103.2.3, UPC 2006.
2. A dual-check valve is not approved for use with a carbonated beverage dispenser. Reference: Section 603.4.12 and Table 6-2 (high hazard, back-siphonage, back-pressure), UPC 2006.
3. Provide cleanouts sized per Section 707.11, UPC 2006 (both restrooms show a 4" waste with only a 3" cleanout).
4. Show how the indirect waste piping manifold (serving the hot buffet table, cold table and the ice bin) complies with the requirements of Section 801.2.3 with respect to food handling fixtures having separately piped indirect waste drains.
5. The 1500-gallon gravity grease interceptor appears to have been sized for use by multiple restaurants or is over-sized for the current use. If multiple restaurants are to be using the interceptor, provide a copy of the approved petition of appeal to the building official that allows multiple users along with the projected future load for the interceptor. If the interceptor has been over-sized, show how the interceptor will be protected from the development of hydrogen sulfide gas caused by anaerobic conditions. Reference: Sections 306.1 and 1014.3.4.3, UPC 2006.
6. The natural gas branch piping serving the water heater appears to be under-sized. Size natural gas pipe per Section 1217.1, UPC 2006 or provide calculations demonstrating conformance to Section 1217.3, UPC 2006.
04/14/2009 ROBERT SHERRY WATER REVIEW Approved
04/16/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved