Permit Number: T09CM00539
Parcel: 105110630

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM00539
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2009 MARTIN BROWN FIRE REVIEW Approved
03/17/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/17/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
03/25/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. Provide an approved appeal to the building official if the plans are to be reviewed to the 2006 IPC.
03/25/2009 ROBERT SHERRY WATER REVIEW Denied 1. Provide the size of the existing water meter and the total connected water demand that will result from the addition of this activity. Reference: Sections 610.1 and 610.2, UPC 2006.
2. Show the location of the reduced pressure backflow assembly on the drawings and indicate the size of the assembly. Reference: City of Tucson Ordinance 9976, Backflow Prevention and Cross-connection Control.
03/26/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the ventilation calculation for HP-1 to include the System Ventilation Efficiency (Ev) correction. Reference: Sections 6.2.5.2 through 6.2.5.4, ASHRAE 62.1-2004.
2. Clarify the relationship of the roof framing drawing (S1) with the mechanical floor plan (M1) with respect to the locations of the mechanical equipment and hoods. The plans show what appear to be two different buildings. Reference: Section 103.2.3, UPC 2006.
3. Correct the labeling for EF-4 on sheet M1. Reference: Section 103.2.3, UPC 2006.
03/30/2009 GERRY KOZIOL WWM REVIEW Approved
04/06/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved