Permit Number: T09CM00505
Parcel: 106011330

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T09CM00505
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2009 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 4-14-09
Activity: T09CM00505
Address: 3718 N. Mesquite Pl #1
Applicant: Timothy Roell

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

FLOOR PLANS:
2. Provide sufficient emergency escape/rescue openings from sleeping rooms, R310. Minimum net opening of 5.7square feet for floors above grade level, 5 square feet for floors at grade level. Maximum sill height = 44". Minimum net clear opening = 24" high x 20" wide.
3. Specify nonabsorbent wall surface minimum 6' above the floor with fiber-cement board backing in tub/shower enclosures, R307.2, R702.4.2.

FOUNDATION PLANS:
4. Provide a note for termite treatment, R320 as amended.

PLUMBING PLAN:
5. Provide a water supply piping diameter sized for the proposed demand, UPC Table 6-6.
6. Include the clothes dryer on the gas appliance schedule.
7. Water conservation requirements: Water closets = 1.6 gallons per flush, Sinks/ Showerheads = 3 gpm, UPC State Amend. 45-312.
8. Shower and tub/shower combinations that have individual control valves shall be of the pressure balance or thermostatic mixing valve type.

MECHANICAL PLAN:
9. Provide combustion air for the utility room containing fuel gas appliances, M1702.2.
10. Show supply and return air ducts with a minimum R-8 insulation, R1103.2.1.

ELECTRICAL PLAN:
11. The required 20-amp circuit supplied for the laundry room receptacles shall only serve receptacles in the laundry room, E3603.3.
12. Bedroom outlets shall be protected with combination-type arc-fault breakers (receptacles, lights, and smoke detectors), E3802.12.
13. All receptacles serving counter top receptacles in the kitchen shall be GFCI protected, E3802.

INTERNATIONAL ENERGY CONSERVATION CODE:
14. Specify the "R" value of the insulation in the masonry furr-out wall (min. R=6 when applied interior) consistent with the space provided, N1102.1.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/22/2009 CPIERCE1 OUT TO CUSTOMER Completed
04/22/2009 SUE REEVES REJECT SHELF Completed