Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T09CM00483
Parcel: 12709012E

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM00483
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/05/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not addressed. Many of the diffusers and returns are being removed as part of the demolition in this suite and later reinstalled. Show how the replaced diffusers and returns are to be balanced so as to provide proper ventilation to the suite. The ventilation requirements are being changed for the conference room and for the presentation room. Reference" Sections 106.3.1 and 403.3, IMC 2006.
05/05/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied See comments for T09CM00482, since plans are on same sheet, same comments apply.

Ray T Majuta
5-08-09