Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM00483
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/10/2009 | GERRY KOZIOL | WWM | REVIEW | Passed | |
03/11/2009 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
03/12/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SEE BUILDING COMMENTS FOR ACTIVITY NUMBER T09CM00482. |
03/12/2009 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Approved | |
03/17/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T09CM00483 6245 E Broadway Bl , Office T I The electrical plans for this project been denied for the following items: 1. There is no electrical circuitry drawn in for the lights, receptacles, or any other electrical equipment to be used. If new circuits are to be added include to which panels they will be added to, the circuit numbers they will be assigned to, and load change to the panel. If they are existing and to be relocated please note on plan. Ray T Majuta Elect Plan Ck DSD City of Tucson 3-17-09 520-837-4988 |
04/01/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/01/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
04/01/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Many of the diffusers and returns are being removed as part of the demolition in this suite and later reinstalled. Show how the replaced diffusers and returns are to be balanced so as to provide proper ventilation to the suite. Reference" Sections 106.3.1 and 403.3, IMC 2006. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/30/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |
04/30/2009 | SUE REEVES | REJECT SHELF | Completed |