Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/05/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/05/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 6245 E broadway Bl
T09CM00482
Office TI

Electrical plans denied for the following:
1. There are no electrical plans shown for the power and lighting remodel.
2.Sheet M1.2 shows a new CU-1 unit, no electrical to it.
3.Sheet M1.2 shows a new DS-1 unit, no electrical.
4.Sheet M1.2 shows a new condensate pump, no electrical.
5. Anew water heater is shown on Sheet P1.2, no electrical.


Ray T Majuta
DSD City of Tucson
Electrical Plan CK
5-08-09
05/05/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Correct detail 4/AE201which still shows an indirect waste receptor, water filter, and an ice machine being installed inside of a cabinet. Revise the detail to coordinate with the plumbing design (sheets P1.1 and P1.2).
05/11/2009 GERRY KOZIOL WWM REVIEW Approved