Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T09CM00482
Parcel: 12709012E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM00482
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2009 GERRY KOZIOL WWM REVIEW Denied need plumbing drawings
03/12/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET AE201; PARTITION G1/G2/G3 DETAILS: INDICATE IN THESE DETAILS HOW THE TOP AND BOTTOM OF THE PARTITION WALLS ARE CONNECTED TO THE STRUCTURE ABOVE AND BELOW TO RESIST LATERAL LOADS SPECIFIED IN THE 2006 IBC SECTION 1607.13. INCLUDE ALL BRACE MEMBER SIZES, CONNECTIONS OF THE BRACES (INCLUDING CONNECTOR SIZE AND QUANTITY) TO THE TOP OF THE PARTITION WALL AND TO THE STRUCTURE ABOVE, AND THE CONNECTOR SIZE AND QUANTITY FOR THE PARTITION WALL TO THE FLOOR STRUCTURE BELOW.
03/12/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
03/17/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T09CM00482

6245 E Broadway Bl , Office T I

The electrical plans for this project have been denied for the following items,

1. There is no electrical circuitry drawn in for the lights, receptacles, or any other electrical equipment to be used. If new circuits are to be added include to which panels they are to be added to, the circuit numbers they will be assigned to, and load change to the panel. If they are existing and to be relocated please note on plan.


Ray T Majuta
Elect Plan Ck
DSD City of Tucson
3-17-09
520-837-4988
04/01/2009 ROBERT SHERRY WATER REVIEW Approved
04/01/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Detail 4/AE201 shows an indirect waste receptor being installed inside of a cabinet. Revise the design to comply with the requirements of Section 804.1, UPC 2006.
2. Show how the new sink being installed in room 505 is to be plumbed (e.g. water and drain piping). Reference: Section 103.2.3, UPC 2006.
04/01/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied All of the diffusers and returns are being removed as part of the demolition in this suite and later reinstalled. Show how the replaced diffusers and returns are to be balanced so as to provide proper ventilation to the suite. Reference" Sections 106.3.1 and 403.3, IMC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/30/2009 CPIERCE1 OUT TO CUSTOMER Completed
04/30/2009 SUE REEVES REJECT SHELF Completed