Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T09CM00465
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/30/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | Project: T09CM00465 7095 E 22 nd ST Electrical plans denied for the following; 1. Total load calculations equal 183.6 amps Total load Pnl A 168.1 amp clarify difference. 2.The revised sheet for panel A does not include the load for existing panel BP. 3. Provide full panel schedules and loads in them for all three panels. 4. How were load trimmed of previous loads shown. 5. Loads for HP-1 does not coincide with the Mechanical sheet load for the unit. Ray T Majuta Elec Pl Ck, PDS 9/30/09 520-837-4988 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/16/2009 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 10/16/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 10/16/2009 | DELMA ROBEY | REJECT SHELF | Completed |