Permit Number: T09CM00441
Parcel: 13322500G

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM00441
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/13/2010 GERRY KOZIOL WWM REVIEW Denied 1:IN & OUT BURGER- ISSUED W/ GREASE INTERCEPTOR & W/ 4" DUMPSTER TRENCH DRAIN COVERED WITH A NON-REMOVABLE HINGED LID.
2:NEEDS WASTEWATER 5TH FLOOR CREDIT EVALUATION FOR EXSISTING RESTAURANT BUILDING DEMO'D.
3:NEEDS 3RD FLOOR PCRWRD REVIEW & APPROVAL OF LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER PER DON WILLHOIT
01/13/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/14/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. The calculations shown on sheet M-3 are incomplete and do not demonstrate compliance with the requirements of Section 403.3, IMC 2006, as amended by the City of Tucson. (Check your records for the ventilation calculations you did for the In-N-Out Burger located at 1979 E Ajo Way in Tucson to see an example of acceptable calculations.)
3. Revise the second sentence of note #6, detail 1/M-5 to comply with Section 506.7, IMC 2006.
01/19/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/28/2010 CPIERCE1 OUT TO CUSTOMER Completed
01/28/2010 SUE REEVES REJECT SHELF Completed