Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - SITE
Permit Number - T09CM00441
Review Name: RESUBMITTAL - SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/15/2009 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 09/17/2009 | RICK MYERS | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show the size, location, and termination of the vent for the grease interceptor. 2. Include the location and size of the RPPBP's for the domestic water as well as the irrigation water. |
| 09/18/2009 | RONALD BROWN | ZONING HC | REVIEW | Approved | At the curb ramp of the marked crossing, the detectable warnings are required to be a minimum of 2' in the direction of travel just like the detectable warning at the opposite end of the marked crossing at the 5'x6' landing. |
| 10/07/2009 | PAUL MACHADO | ENGINEERING | REVIEW | Denied | To: David Little, P.E. DATE: October 7, 2009 4444 E. Broadway Blvd. Tucson, Arizona, 85711 Subject: IN-N-OUT Burger, 7111 E. Broadway Blvd. Site plan T09CM00441 (Third Review) T14S, R15E, Section 08 RESUBMITTAL REQUIRED: Site Plan. The Site Plan (SP) cannot be approved as submitted. Please address the following review comments prior to the next submittal. Site Plan: 1. Please include a response letter to the comments along with the corrected copies of the SP. 2. Per the conversation and the review of the SP at DSD on October 6, 2009 between David Little, Josh Potter of the WLB Group and Paul P. Machado, the following comments were discussed and agreements were made to make the changes that were applicable to the SP. When the plans are re-submitted to the City of Tucson and if the corrections were made, an approval of the SP shall be forth coming. 3. List the disturbance of both sites. Where is it shown on the Site Plan? 4. Show details of all drainage structures in the DR, including basins and weir details. Show details on how the stormwater discharges from the basins. 5. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10. 6. Fully dimensioned loading space(s) and maneuvering area(s) for the refuse service vehicles per D.S. 2-02.2.1.14. 7. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19. 8. Add to the Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23. 9. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. The new trash and compact enclosure cannot be accessed by the service vehicle. The max. straight and clear back up distance of 50' for the service vehicle is required. Obtain permission of from environmental services for the location of the trash compactor, it does not meet D.S. listed above. Contact Andy Vera at 791-3785 or Andy.Vera@tucsonaz.gov 10. Call out the standard detail number for the refuse enclosure detail 2/7. Also the refuse enclosure requires side wall bollards for wall protection. Drainage Report: 1. The DR has been accepted conditionally on the following comment. 2. Site Plan comment no. 2 above applies to the DR also. 3. Show details of all drainage structures in the DR, including basins and weir details. If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov Paul P. Machado Senior Engineering Associate City of Tucson/Development Services Department 201 N. Stone Avenue P.O. Box 27210 Tucson, Arizona 85726-7210 (520) 837-4932 office (520) 879-8010 fax C:/7111 E. Broadway Blvd. 3 SITE |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/08/2009 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 10/08/2009 | SUE REEVES | REJECT SHELF | Completed |