Permit Number: T09CM00440
Parcel: 132081560

Address:
1979 E AJO WY

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T09CM00440
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/06/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/10/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: IN N OUT BERGER
T09CM00440---1979 E AJO WY

The Electrical Plans have been denied for the following:

1. As per NEC 110 .14, C, 1(b), Termination provisions of equipment for circuits rated over 100 amperes,---.
"(2) Conductors with higher temperature ratings, provided the ampacity of such conductors does not exceed the 75 degree C (167F) ampacity of the conductor size used, or up to their ampacity if the equipment is listed and identified for use with such conductors," The information sent by Mr. Kevin Uriuoli on 11/10/09 by e-mail did not show that the equipment (switchgear) was listed for the higher temperature.
All other items ok.

Ray T Majuta
DPSD City of Tucson,
Elect Pln Ck
11/10/09
Ray.Majuta@tucsonaz.gov