Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM00440
Parcel: 132081560

Address:
1979 E AJO WY

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T09CM00440
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/30/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Sheet P-5 indicates ¾" HW and CW outlets being provided on the roof for use with a pressure washer. Revise sheet P-8 to reflect this change and indicate how backflow protection will be provided. Clarify if there will now be a total of three possible locations for a pressure washer.
2. Sheet K-8.1, detail 11 shows the reduced pressure principle backflow preventers are located greater than 5'-0" above the finished floor. Locate the reduced pressure backflow preventers to conform to the access and clearance requirements of Section 603.3.4, UPC 2006.
3. The revised kitchen sheets indicate additional floor sinks, floor drains, hose bibbs, and gas outlets. Clarify what is actually new and coordinate the plumbing drawings if necessary
09/30/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Sheet A5.0 indicates that a wood-stud wall is located within 18" of a Type I hood. Section 507.9, IMC 2006 allows for zero clearances only with non-combustible supports in the wall, e.g. metal studs.
10/09/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: IN N OUT BURGER
1979 E Ajo Wy--- T09CM00440
Electrical Plan CK

The Electrical Plans have been denied for the following:

1. Sheet E1.0 Note 2, on Site Reference, only two sets of 4-500 Kcmil noted as service entrance conductors . The ampacity for 500 Kcmil conductors under the 75 C column on table 310-16 2005 NEC show 380 amps x 2= 760 amps. The total load shown is 813 amps.
Note , the 2005 NEC 240.4 (C) states, if overcurrent device is rated at over 800 amps the ampacity of the conductors is to be equal or greater than the overcurrent
device.
2.Sheet E4.0 , Circuit 38 in the self serving bar area needs Panel Designation.
3. Sheet E5.0 , the receptacles on this sheet have no panel designations as they had on previous plans,
4. The new set of plans appears to be missing sheets E8,E9,and E10.



Ray T Majuta
Electrical Plan Check
PDSD City of Tucson
10/11/09,
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
11/05/2009 CINDY AGUILAR APPROVAL SHELF Completed
11/05/2009 CINDY AGUILAR OUT TO CUSTOMER Completed