Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T09CM00440
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/29/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/30/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Sheet P-5 indicates ¾" HW and CW outlets being provided on the roof for use with a pressure washer. Revise sheet P-8 to reflect this change and indicate how backflow protection will be provided. Clarify if there will now be a total of three possible locations for a pressure washer. 2. Sheet K-8.1, detail 11 shows the reduced pressure principle backflow preventers are located greater than 5'-0" above the finished floor. Locate the reduced pressure backflow preventers to conform to the access and clearance requirements of Section 603.3.4, UPC 2006. 3. The revised kitchen sheets indicate additional floor sinks, floor drains, hose bibbs, and gas outlets. Clarify what is actually new and coordinate the plumbing drawings if necessary |
09/30/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Sheet A5.0 indicates that a wood-stud wall is located within 18" of a Type I hood. Section 507.9, IMC 2006 allows for zero clearances only with non-combustible supports in the wall, e.g. metal studs. |
10/09/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: IN N OUT BURGER 1979 E Ajo Wy--- T09CM00440 Electrical Plan CK The Electrical Plans have been denied for the following: 1. Sheet E1.0 Note 2, on Site Reference, only two sets of 4-500 Kcmil noted as service entrance conductors . The ampacity for 500 Kcmil conductors under the 75 C column on table 310-16 2005 NEC show 380 amps x 2= 760 amps. The total load shown is 813 amps. Note , the 2005 NEC 240.4 (C) states, if overcurrent device is rated at over 800 amps the ampacity of the conductors is to be equal or greater than the overcurrent device. 2.Sheet E4.0 , Circuit 38 in the self serving bar area needs Panel Designation. 3. Sheet E5.0 , the receptacles on this sheet have no panel designations as they had on previous plans, 4. The new set of plans appears to be missing sheets E8,E9,and E10. Ray T Majuta Electrical Plan Check PDSD City of Tucson 10/11/09, Ray.Majuta@tucsonaz.gov |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/05/2009 | CINDY AGUILAR | APPROVAL SHELF | Completed |
11/05/2009 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |