Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM00438
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/03/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. ACCESSIBLE SIGNAGE TO BE 7' A.F.G. AND ADD A "VAN ACCESSIBLE" SIGN 2. PROVIDE ANOTHER EXIT 1/2 THE DIAGONAL DISTANCE FROM THE EXISTING FRONT EXITS, SECTION 1015.2.1 3. PRROVIDE A STRUCTURAL EVALUATION OF NEW ROOF TOP UNIT REPLACEMENT OF EXISTING HVAC UNIT. |
| 03/03/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference: Section 403.2.1, IMC 2006. |
| 03/03/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/03/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/03/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 03/03/2009 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Approved | |
| 03/03/2009 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 03/13/2009 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 03/13/2009 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
| 03/13/2009 | CPIERCE1 | ENGINEERING | REVIEW | Needs Review | |
| 03/13/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 03/13/2009 | MARTIN BROWN | FIRE | REVIEW | Approved |