Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM00435
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/03/2009 | DAVE MANN | FIRE | REVIEW | Denied | Corridor at north end of suite required to 1 hour fire rated. Please refer to 2006 IFC, Section 1017 and table 1017.1 |
| 03/03/2009 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/11/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 03/18/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/25/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/25/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | If the building energy compliance is not in accordance with ASHRAE 90.1, the duct insulation shall be determined by Section 503.2.7, IECC 2006, as amended by the City of Tucson. Reference: Section 501.2, IECC 2006, as amended by the City of Tucson. |
| 03/25/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2006, for business occupancy (e.g. drinking fountain). |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/27/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 03/27/2009 | SUE REEVES | REJECT SHELF | Completed |