Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM00418
Parcel: 122160020

Address:
3530 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM00418
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
02/25/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation for the salon per Section 403.3, IMC 2006.
2. Provide a vent for the clothes dryer.
02/25/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Denied 1. SEE BUILDING COMMENTS.
02/25/2009 ROBERT SHERRY WATER REVIEW Approved
02/25/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEETA-2: INTERIOR WALL IS REQUIRED TO BE BRACED AT THE TOP TO RESIST LATERAL LOADS PER THE IBC SECTION 1607.13. INCLUDE IN THE DETAIL THE BRACING SIZE AND SPACING, THE CONNECTOR SIZE AND QUANTITY FOR THE BRACE TO THE STRUCTURE ABOVE AND TO THE TOP OF THE WALL, AND THE CONNECTION SIZE AND SPACING AT THE BOTTOM OF THE WALL.
02/25/2009 JASON GREEN ENGINEERING REVIEW Approved
02/25/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, and valves. Reference: Sections 103.2.3, 605.5, 608.3, and 608.7 UPC 2006
02/25/2009 MARTIN BROWN FIRE REVIEW Approved
02/25/2009 ERIC NEWCOMB ADA REVIEW Passed
03/02/2009 GERRY KOZIOL WWM REVIEW Approved
03/02/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
03/02/2009 CAGUILA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review