Permit Number: T09CM00408
Parcel: 13315062F

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM00408
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/03/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PER PREVIOUS COMMENT, THE SQUARE FOOTAGE USED IN THIS PROJECT IS NOT CLEAR. THERE ARE THREE NUMBERS LISTED ON THE DRAWINGS. CLARIFY.
2. PER PREVIOUS COMMENT, IT DOES NOT APPEAR THE 5' DIAMETER TURNING RADIUS IS MET WITH THIS RESTROOM CONFIGURATION. CLARIFY.
3. PER PREVIOUS COMMENT, NEED CONNECTION SIZE/SPACING/QUANTITY FOR BRACE TO EXISTING STRUCTURE, FOR BRACE TO TOP OF PARTITION, AND FOR PARTITION TO FLOOR.
4. ADD RESPONSE LETTER FOR NEXT REVIEW, ADDRESSING EACH ITEM LISTED HERE.
03/03/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Denied 1. SEE BUILDING COMMENTS.
03/03/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2006, for a business occupancy.
03/04/2009 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/04/2009 DELMA ROBEY OUT TO CUSTOMER Completed