Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM00408
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/24/2009 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 02/24/2009 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 02/25/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/25/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/25/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. CONFLICT IN SQUARE FOOTAGE OF THE PROJECT. IT APPEARS THE 1800 SF IS CORRECT, WHICH REQUIRES SEPARATE RESTROOM FACILITIES FOR MEN AND WOMEN PER IBC 2902.2. IT IS UNCLEAR HOW THE 1350 SF NOTED IN THE CODE ANALYSIS DATA IS VERIFIED. 2. VERIFY THE REQUIRED TURNING SPACE IN THE RESTROOMS FOR ACCESSIBILITY IS MET PER ANSI SECTION 304. SHOW THIS ON THE PLAN. 3. SECTION C ON SHEET A1.0: BRACE TOP OF WALL TO RESIST LATERAL FORCES PER IBC SECTION 1607.13. INDICATE BRACING SIZE AND SPACING, CONNECTION OF BRACING TO THE TOP OF THE PARTITION WALL AND TO THE EXISTING STRUCTURE, AND CONNECTION OF THE WALL TO THE FLOOR (SIZE AND SPACING). 4. PROVIDE TWO SETS OF DRAWINGS FOR REVIEW. |
| 02/25/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/25/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Install the vacuum breaker for the water heater in accordance with the manufacturer's listing information (i.e. no valves to be between the water heater and the vacuum breaker). 2. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2006, for a business occupancy. |
| 02/25/2009 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/25/2009 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
| 02/25/2009 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 03/02/2009 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 03/02/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |