Permit Number: T09CM00408
Parcel: 13315062F

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM00408
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2009 STEVE SHIELDS ZONING REVIEW Approved
02/24/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
02/25/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/25/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/25/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. CONFLICT IN SQUARE FOOTAGE OF THE PROJECT. IT APPEARS THE 1800 SF IS CORRECT, WHICH REQUIRES SEPARATE RESTROOM FACILITIES FOR MEN AND WOMEN PER IBC 2902.2. IT IS UNCLEAR HOW THE 1350 SF NOTED IN THE CODE ANALYSIS DATA IS VERIFIED.
2. VERIFY THE REQUIRED TURNING SPACE IN THE RESTROOMS FOR ACCESSIBILITY IS MET PER ANSI SECTION 304. SHOW THIS ON THE PLAN.
3. SECTION C ON SHEET A1.0: BRACE TOP OF WALL TO RESIST LATERAL FORCES PER IBC SECTION 1607.13. INDICATE BRACING SIZE AND SPACING, CONNECTION OF BRACING TO THE TOP OF THE PARTITION WALL AND TO THE EXISTING STRUCTURE, AND CONNECTION OF THE WALL TO THE FLOOR (SIZE AND SPACING).
4. PROVIDE TWO SETS OF DRAWINGS FOR REVIEW.
02/25/2009 ROBERT SHERRY WATER REVIEW Approved
02/25/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Install the vacuum breaker for the water heater in accordance with the manufacturer's listing information (i.e. no valves to be between the water heater and the vacuum breaker).
2. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2006, for a business occupancy.
02/25/2009 MARTIN BROWN FIRE REVIEW Approved
02/25/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Denied 1. SEE BUILDING COMMENTS.
02/25/2009 ERIC NEWCOMB ADA REVIEW Passed
03/02/2009 CAGUILA1 WWM REVIEW Needs Review
03/02/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review