Permit Number: T09CM00402
Parcel: 14117690A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM00402
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2009 STEVE SHIELDS ZONING REVIEW Approved
04/02/2009 ROBERT SHERRY WATER REVIEW Approved
04/02/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The architectural design for the mounting shelf for the water heater was not accompanied with structural calculations to show that the water heater is safely supported and does not indicate either the construction of the existing wall (metal or wood studs?) or the method of attaching the blocking to the existing studs. Reference: Sections 310.0 and 314.5, UPC 2006.
2. The letter from the mechanical engineer approves deletion of "all isolation valves and water hammer arrestors". Isolation valves are required before all appliances and water hammer arrestors are required to be installed as close as possible to quick-acting valves (e.g. clothes washer supplies). Show which isolation valves and which water hammer arrestors are to be deleted. Reference: Sections 103.2.3, 605.0, and 609.10, UPC 2006.