Permit Number: T09CM00398
Parcel: 14043011A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM00398
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2009 STEVE SHIELDS ZONING REVIEW Passed
02/23/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the ventilation calculations to take into account the different occupancy loads in the project space. Reference: Sections 403.3 and 403.3.2, IMC 2006.
02/23/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/23/2009 RMYERS1 WATER REVIEW Approved
02/23/2009 JWILLIA5 BUILDING-COMMERCIAL REVIEW Denied 1. REVIEW DEAD END REQUIREMENTS PER IBC SECTION 1017.3 (2). DOES THE DEAD END CORRIDOR LENGTH EXCEED 50'? CLARIFY.
2. CHANGE PLAN DRAWING SCALE TO 1/4".
02/23/2009 RMYERS1 WWM REVIEW Completed no new plumbing fixtures
02/23/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Passed
02/23/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
02/23/2009 JWILLIA5 ZONING HC SITE REVIEW Denied 1. SEE BUILDING COMMENTS.
02/23/2009 JWILLIA5 ADA REVIEW Passed
02/26/2009 CPIERCE1 FIRE REVIEW Needs Review
02/26/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review