Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM00355
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/04/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved. The condensate drains for AC-1 and AC-2; appear to be combined. If they are combined, the minimum size of the combined drain is 1", not 3/4". Reference: Section 307.2.2, IMC 2006, as amended by the City of Tucson. |
03/04/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved. The proposed design does not indicate the width of the supporting bracket (typically this type of bracket is less than 8" wide), the required size and type of bolts for this application, or the type of wall on which the water heater is to be mounted. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006. 2. Comment not resolved; the T&P valve has nothing to do with a vacuum relief. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/10/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
03/10/2009 | SUE REEVES | REJECT SHELF | Completed |