Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T09CM00352
Parcel: 14026045A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM00352
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not resolved. See the local amendment to Section 307.2.2 which includes the note: When two or more units are tied together, the minimum drain size shall be 1". Reference: Section 307.2.2, IMC 2006, as amended by the City of Tucson.
2. Comment not resolved; see Section 403.3.2, IMC 2006. Revise the ventilation calculations to take into account the different occupancy loads in the project space (i.e. AC-4, which serves the conference room, an office, and a corridor, has inadequate ventilation air). Reference: Sections 403.3 and 403.3.2, IMC 2006.
03/04/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved. The proposed design does not indicate the width of the supporting bracket (typically this type of bracket is less than 8" wide), the required size and type of bolts for this application, or the type of wall on which the water heater is to be mounted. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
2. Comment not resolved; the T&P valve has nothing to do with a vacuum relief. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/10/2009 DELMA ROBEY OUT TO CUSTOMER Completed
03/10/2009 SUE REEVES REJECT SHELF Completed