Review Date Reviewer's Name Type of Review Description Status Comments
02/17/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/18/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 19 FEBRUARY 2009
T09CM00351/MacARTHUR BUILDING
REVIEWED BY RON BROWN

CODE REVIEW
2006IBC/ICC ANSI 117.1

DENIED: SEE COMMENTS BELOW

A. INSURE OWNER FURNISHED RECEPTION COUNTER IS ACCESSIBLE
B. PROVIDE A COMPLETE CODE SEARCH ANALYSIS SHOWING ALL REQUIRED FIRE RATED BUILDING COMPONENTS.
C. SHOW AND IDENTIFY ALL REQUIRED FIRE RATED COMPONENTS, ROOMS, VERTICAL SHAFTS AND PARTITIONS, NEW AND EXISTING ON ALL THREE FLOOR PLANS.
D. SHOW HOW RATED VERTICAL SHAFTS ARE TERMINATED AT RATED FLOOR LEVELS AND OR PASS THROUGH FLOOR LEVELS.
E. PROVIDE DETAILED WALL SECTIONS OF ALL RATED PARTITIONS, NEW AND USED AND SHOW ALL FIRE RATING COMPONENTS OF PARTITION AND O.C. OF ALL METAL STUDS.
F. CONFIRM AND INDICATES FIRE RATING OF NEW AND EXISTING DOORS AND FRAMES LOCATED IN ALL FIRE RATED PARTITIONS.
G. SHOW A DETAIL OF RATED EXTERIOR BEARING WALLS AS REQUIRED BY TABLES 601 AND 602.
H. PROVIDE INSULATION AROUND ALL EXPOSED LAVATORY PIPING.
I. SHEETS S2.1 AND S3.1: PROVIDE NEW MASONRY WALL AND WALL FOOTING DESIGN CALCULATIONS. PROVIDE CALCULATIONS FOR LINTEL LT1.
J. SHEET S2.1; SHEET S5.1 (DETAIL 105): THE SECTION INDICATES THE WALL FOOTING EXTENDS PAST THE EXISTING STEEL COLUMN, WHILE THE PLAN DOES NOT INDICATE THAT CONDITION. CLARIFY.
K. SHEET S3.1; STAIR FRAMING PLAN: ADD A BEAM MARK (B3) TO THE BEAMS ON EITHER SIDE OF THE STAIR AT THE WEST END (STAIR STRINGERS).

END OF REVIEW
02/18/2009 RONALD BROWN ZONING HC SITE REVIEW Denied reference building comments
02/18/2009 RONALD BROWN ADA REVIEW Passed NOT A COT PROJECT
02/19/2009 ROBERT SHERRY WATER REVIEW Approved
02/19/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Include all of the existing plumbing fixtures and water-consuming appliances (e.g. 3 mop sinks and a dishwasher) in the demand calculations. Reference: Section 610.1, UPC 2006.
2. Provide a low-pressure cutoff switch for the water pressure booster pump system. Reference: Section 609.8, UPC 2006.
3. Correct the water pressure calculations; based on 65 PSI available after the booster pump, the total allowable pressure for friction is 20.5 PSI, not 25.0 PSI. Reference: Section 610.1, UPC 2006.
4. Complete the detail call-out bubbles on sheet P1.
02/19/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the fan coil, FC-1, is to be connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006.
2. Coordinate the mechanical roof plan with the architectural roof plan. The plans currently show interferences and encroachment of the required maintenance space for the mechanical units and the proposed photovoltaic panels. Show the required maintenance access space for the equipment in accordance with the manufacturer's installation instructions. Reference: Sections 106.3.1 and 304.1, IMC 2006.
3. Provide a mechanical and electrical design for fan coil, FC-2, and for its condensing unit, CU-2. Show the size, route, and termination of its condensate drain. Reference: Section 106.3.1, IMC 2006.
4. Provide listed and labeled fire dampers for protection of ducts and penetrations of fire resistive walls (e.g. the elevator equipment room). Reference: Sections 607.3, and 607.5.2, IMC 2006.
5. Show how the vertical penetrations of the floor/ceiling assemblies by the exhaust duct for EF-1 are to be protected. Reference: Section 707.4, IBC 2006.
6. Details 6 and 7 on sheet M7 refer to existing exhaust fans and air conditioning units that are to be modified. Show the locations for these items on the drawings. Reference: Section 106.3.1, IMC 2006.
02/20/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/23/2009 GERRY KOZIOL WWM REVIEW Approved