Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T09CM00311
Parcel: 125031160

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T09CM00311
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2009 GERRY KOZIOL WWM REVIEW Approved
06/26/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. CALCULATIONS: PROVIDE DESIGN KEY PLAN IN THE CALCULATIONS FOR ROOF FRAMING, FLOOR FRAMING, FOUNDATION, AND SHEAR WALLS TO ASSIST PLANS EXAMINERS IN THE REVIEW OF THESE PLANS.
2. CALCULATIONS: DID NOT FIND AN ANALYSIS OF THE EXISTING FOUNDATION UNDER THE NEW FLOOR AND ROOF LOADS AT THE ART STUDIO.
3. CALCULATIONS: DID NOT LOCATE CALCULATIONS FOR THE NEW EXTERIOR WALL FOUNDATIONS AT THE BEDROOM ADDITION. VERIFY AND PROVIDE.
4. SHEET S-3 (PLAN 2); CALCULATIONS: THE HEADERS OVER THE OPENINGS AT THE BALCONY COULD NOT BE LOCATED IN THE CALCULATIONS. PROVIDE.
5. SHEET S-3; PERGOLA: PROVIDE DESIGN CALCULATIONS FOR THE PERGOLA ROOF AND FOUNDATION.
6. SHEET S-4; DETAIL 1: PROVIDE THE ANGLE BRACE SIZE AND SPACING, ALONG WITH THE CONNECTION SIZE AND QUANTITY OF CONNECTORS AT THE TOP AND BOTTOM OF THE BRACE.
7. SHEET S-5; SECTION 02200: THE CITY OF TUCSON AMENDMENTS TO THE 2006 IBC SECTION 1805.2 REQUIRE THAT THE MINIMUM DEPTH OF FOOTINGS BELOW UNDISTURBED GROUND SURFACE SHALL BE 18" FOR 1500 PSF ALLOWABLE SOIL BEARING PRESSURE. VERIFY THAT THE DESIGN AND DETAILS FOLLOW THIS REQUIREMENT.
8. CALCULATIONS: THE HEADER OVER THE NEW DOUBLE DOOR OPENING AT THE DINING ROOM COULD NOT BE LOCATED IN THE CALCULATIONS. PROVIDE.
9. PROVIDE WRITTEN RESPONSES FOR ALL REVIEW COMMENTS.
06/29/2009 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 6-30-09
Activity: T09CM00311
Address: 3033 E. 3rd St.
Applicant: Diane Carhuff

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

SITE PLAN:
3. Show compliance with the pool enclosure requirements according to AG105.2 as amended by the City of Tucson. Include the height of the barrier and all windows/doors within the pool area.
4. Include the proposed pergola in the lot coverage calculation.
5. Demonstrate appropriate fire resistance for the pergola near the property line. Exterior walls with a fire separation distance less than 3 feet shall have not less than a one-hour fire-resistive rating with exposure from both sides. Projections shall not extend to a point closer than 2 feet from the line used to determine the fire separation distance. Projections extending into the fire separation distance shall have not less than one-hour fire-resistive construction on the underside. (R302.1 as amended)

FLOOR PLANS:
6. Specify doors between the garage and living space to be self-closing minimum 20-minute fire-rated. (R309.1 as amended)
7. Specify safety glazing in hazardous locations within 24" of doorways. (R308.4)

STRUCTURAL PLANS:
8. Provide 50-80% of the required roof ventilation in the upper portion of the roof to qualify for the 1:300 ratio. (R806.2)

PLUMBING PLAN:
9. The Uniform Plumbing Code and the International Plumbing Code are not interchangeable. Only one code may be specified for a plumbing design. Notes provided indicate plumbing to comply with the UPC and the fixture unit schedule has IPC values. Clarify.
10. Justify the specified ½" diameter hot and cold supply lines to the new bathroom. (P2903.7)

ELECTRICAL PLAN:
11. Provide accurate circuit references on electrical layout to match panel schedules. (E3603.5)

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/13/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
07/13/2009 FFIGUER1 REJECT SHELF Completed