Permit Number: T09CM00283
Parcel: 14002010A

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T09CM00283
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2009 RONALD BROWN ZONING HC SITE REVIEW Denied 1. West entrance ramp and landing:
Comments on large scale details shown on Sheet A-2
a. Strike side of door on the outside must have 18" clearance as per ANSI 117.1, Section 404.2.3.1 (a).
b. Contimue handrails to face of building wall.
c. 5'-0" clearance is from inside face of handrail to inside face of handrail.
2. North entrance ramp and landing to Patio:
a. Continue handrail around side and top of landing to patio edge.
b. Provide handrail on both sides of ramp.
c. Provide 5'-0" clearance from inside face of handrail to inside face of handrail at landing.
05/22/2009 PAUL MACHADO ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/09/2009 DELMA ROBEY OUT TO CUSTOMER Completed
06/09/2009 SUE REEVES REJECT SHELF Completed