Permit Number: T09CM00283
Parcel: 14002010A

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T09CM00283
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2009 DAVE MANN FIRE REVIEW Approved
04/02/2009 STEVE SHIELDS ZONING REVIEW Approved
04/03/2009 RONALD BROWN ZONING HC SITE REVIEW Denied 1. A COPY OF THE LAST APPROVED SITE PLAN WAS REQUESTED SO THE EFFECTS OF THE NEW ADDITION COULD BE EVALUATED. AS THERE ARE NONE, AN AERIAL SITE PLAN REVIEW WAS CONDUCTED THROUGH "PRO".
2. THERE ARE EXISTING (3 TO 4) ACCESSIBLE PARKING SPACES THAT WILL BE ELIMINATED DUE TO THE NEW CONSTRUCTION THAT ARE NOT SHOWN TO BE REPLACED IN THE MODIFIED SITE PLAN. AS PER IBC 2006, CHAPTER 11 REQUIREMENTS, TWO ACCESSIBLE SPECES ARE REQUIRED PER THE NUMBER OF PARKING SPACES PROVIDED. PLEASE INCLUDE THESE ACCESSIBLE SPACES ALONG WITH CONNECTION TO AN ACCESSIBLE ROUTE TO THE ACCESSIBLE ENTRANCES OF THE BUILDING.
04/13/2009 PETER MCLAUGHLIN LANDSCAPE REVIEW Passed
04/13/2009 PETER MCLAUGHLIN NPPO REVIEW Passed
04/14/2009 PAUL MACHADO ENGINEERING REVIEW Denied To: Intertech DATE: April 14, 2009
6089 E. Grant Road
Tucson, Arizona 85712

Subject: Fleet Building Expansion,3950 E. Irvington Rd.
Site plan T09CM00283 (Second Review)
T15S, R14E, Section 03

RESUBMITTAL REQUIRED: Site Plan.

Site Plan:

1. The SP has been conditionally approved. Correct the plans and re-submit.
2. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10. The future face of curb for a 150' wide Right-of-way is 12' from the property line. Revise as required.
3. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19.
4. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21. Show the ingress/egress as it is existing and per the Irvington Road improvement plans included in the set.

Drainage Statement:
1. The DS has been accepted by engineering.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
3950 E. Irvington Rd_site_2
04/22/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/24/2009 DELMA ROBEY OUT TO CUSTOMER Completed
04/24/2009 SUE REEVES REJECT SHELF Completed