Permit Number: T09CM00283
Parcel: 14002010A

Review Status: Completed

Review Details: SITE

Permit Number - T09CM00283
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2009 DAVE MANN FIRE REVIEW Approved
02/06/2009 RBROWN1 ADA REVIEW Passed NOT A COT PROJECT
02/06/2009 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: TEP Fleet Building Expansion
T09CM00283
Site Plan (1st Review)

TRANSMITTAL DATE: February 9, 2009

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC). Per D.S. 2-02.2.2.B When the proposed site is part of a larger site, the calculations encompass the entire site, whether existing or proposed. This said as a copy of the last approved overall site plan was not provided and all calculations are not based on the entire site zoning cannot verify if full code compliance is required for the entire site at this time. Once the required calculations for the entire site are provided additional comments may be forth coming.

2. Provide a copy of the last approved site plan.

3. D.S. 2-02.2.1.A.2 Provide a property description (legal description) on the site plan.

4. D.S. 2-02.2.1.A.4 Provide a Location Map that meets the requirements of D.S. 2-05.2.1.D on the site plan.

5. D.S. 2-02.2.1.A.5 Clearly show the property line along Irvington Road on the site plan along with the dimensions and bearings.

6. D.S. 2-02.2.1.A.6 For all existing and proposed buildings and structures, provide the height and identify all canopies and awnings on the site plan.

7. D.S. 2-02.2.1.A.10 Show both existing and future sight visibility triangles (SVTs) on the plan. The Future SVT should be shown based on the location of future curb not as shown on the plan.

8. D.S. 2-02.2.1.A.11 Clearly shown the vehicle and pedestrian circulation on the plan. If vehicle circulation is planned for the north and west side of the proposed expansion than per D.S. 3-05.2.2.B.1 A minimum setback distance of five (5) feet for a pedestrian refuge area must be maintained between any enclosed structure and a PAAL.

9. D.S. 2-02.2.1.A.13 If applicable show the location, type, size, and height of existing and proposed signage.

10. D.S. 2-02.2.1.A.19 Provide a fully dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way for Irvington Road.

11. D.S. 2-02.2.1.A.20 If applicable show all easements of record must be graphically shown on the plan together with recording docket and page reference.

12. D.S. 2-02.2.1.A.25 If applicable show all existing and proposed lighting layout and type.

13. D.S. 2-02.2.1.A.28 Provide existing zoning of parcel and adjacent parcels, including those across streets and alleys.

14. D.S. 2-02.2.1.A.31 Provide the existing and proposed use on the plans. The use should be listed as "UTILITIES USE GROUP, DISTRUBUTION SYSTEM 34, SUBJECT TO SECTION 3.5.11.1.A, .B, AND D.

15. D.S. 2-02.2.2 Per D.S. 2-02.2.2.B When the proposed site is part of a larger site, the calculations encompass the entire site, whether existing or proposed. If the project is being phased, calculations must show that, at each phase, requirements are being met. This said revise all calculation required under D.S. 2-02.2.2 to meet this requirement. Review the requirements listed under Development Designator 34 prior to revising the calculations.

16. Depending on how the above comments are addressed addition comments may be forth coming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t09cm00283

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents.
02/06/2009 RONALD BROWN ZONING HC SITE REVIEW Denied 1. SAME COMMENTS AS ZONING, PLEASE PROVIDE A COPY OF LAST APPROVED SITE PLAN TO REVIEW.
2. SECTION 3907.4.1 REQUIRES NO MORE THAN 20% OF THE PROPOSED CONSTRUCTION COST TO BE ALLOTED TO ACCESSIBILITY UPGRADES. PLEASE PROVIDE A BRAKDOWN OF SAID COSTS SHOWING PERCENTAGES SPENT ON ACCESSIBILITY UPGRADES. WE RECCOMMEND THAT ACCESSIBILITY UPGRADES START WITH EXTERIOR IMPROVEMENTS SUCH AS ACCESSIBLE ROUTES TO THE PUBLIC R.O.W, ACCESSIBLE PARKKING SPACES AND ACCESSIBLE ELEMENTS FOR ENTERING THE BUILDING.
02/24/2009 PETER MCLAUGHLIN LANDSCAPE REVIEW Approved
03/02/2009 PETER MCLAUGHLIN NPPO REVIEW Passed
03/04/2009 PAUL MACHADO ENGINEERING REVIEW Denied To: Intertech DATE: March 6, 2009
6089 E. Grant Road
Tucson, Arizona 85712

Subject: Fleet Building Expansion, 950 E. Irvington Rd.
Site plan T09CM00283 (First Review)
T15S, R14E, Section 03

RESUBMITTAL REQUIRED: Site Plan and Hydrology Report.

The Site Plan (SP) and Drainage Statement (DS) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. Please provide property description per D.S. 2-02.2.1.3.
3. Please label lot dimensions and bearings per D.S. 2-02.2.1.5.
4. Show all points of egress and ingress including locations and width of driveways and parking area access lanes (P.A.A.L.) per D.S. 2-02.2.1.11.
5. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10.
6. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
7. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19.
8. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.
9. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
10. Show all fences, walls, or vegetation for screening and sight visibility by type, material, height, location and spacing per D.S. 2-02.2.1.27.
11. Show Site plan (T09CM00283) number on all sheets per D.S. 2-02.2.1.29.
12. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
13. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice.
14. List the consulting engineer and the owner/developer on the plans with the pertinent information.
15. Add note: "Depress all landscaped areas 6" maximum for water harvesting".

Drainage Statement:
1. Please include a response letter to the comments along with the corrected copies of the DS.
2. A Drainage Statement is a brief description of drainage conditions applicable for a site which are not affected by 100 year flows of 100 cfs, of more……per S.M.D.D.F.M., chap. II, 2.1.2. The DS must be submitted along with the site plan and accepted with the approval of the grading plan.
3. The content and format of the Drainage Statement should follow S.M.D.D.F.M., chap. II, 2.2.
4. Show the project address or administration address on the cover sheet of the DS.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
3950 E. Irvington Rd_site
03/06/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the location and size of the water meter
b. the location of the main water lines and fire hydrants
c. the location and size of the public sanitary sewer and
d. the location, invert, and rim elevation of all manholes and cleanouts.
Reference: City of Tucson Development Standard No. 2-05.0 2.3 and Section 103.2.3, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/11/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
03/11/2009 SUE REEVES REJECT SHELF Completed