Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/NPPO
Permit Number - T09CM00259
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/03/2009 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T09CM00259 3/3/09 2020 S. CAMPBELL AVE. PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, IECC AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2006 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. STRUCTURAL PLANS: 1. ROOF FRAMING PLAN / 3 ; 2X6 #2DF @ 24"OC APPEAR TO BE INADEQUATE TO SPAN 13'. PLEASE JUSTIFY. 2. ROOF FRAMING PLAN / 3 ; 4X12 #2DF RIDGE BEAM APPEARS TO BE INADEQUATE TO BE OVER SPANNED. PLEASE JUSTIFY. 3. SPECIFY LUMBER GRADE AND SPECIES. 4. ROOF FRAMING PLAN / 3, 4 ; PLEASE CALL OUT THE HEADERS AS BEING DOUBLE OR HAVING 2 MEMBERS. SECTIONS - DETAILS - MISC. NOTES: 1. GENERAL NOTE 5 / 2 ; JUSTIFY THE WINDOW U-VALUE . SEE TABLE N1102.1 2. GENERAL NOTE 8 / 2 ; IF THE CEILING OF THE SHED IS TO BE S/R ed, JUSTIFY THE 4X8 RIDGE BEAM. DETAIL 2/5 INDICATES THE WALLS ARE TO BE S/R ed. 3. PLEASE SPECIFY THE ROOF AND WALL INSULATION . SEE TABLE N 1102.1 MECHANICAL PLANS: 1. PLEASE PROVIDE A SMOKE DETECTOR IN THE HALLWAY. R313.2 ITEM 2 2. PLEASE MOVE THE SMOKE DETECTOR OFF THE A/C CIRCUIT. 3. PLEASE NOTE FOR THE HOME OWNER THAT A SEPARATE PERMIT WILL BE REQUIRED FOR THE A/C. IF IT'S TO BE INCLUDED ON THIS PERMIT, PROVIDE ELECTRICAL AND DUCTS. ELECTRICAL PLANS: 1. MOVE THE SMOKE DETECTOR OFF THE A/C CIRCUIT 2. PROVIDE A SMOKE DETECTOR IN THE HALLWAY. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 837-4910 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/12/2009 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 03/12/2009 | SUE REEVES | REJECT SHELF | Completed |