Permit Number: T09CM00257
Parcel: 12710084B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM00257
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/11/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/12/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed