Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM00257
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/03/2009 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 02/03/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. If the building energy compliance is not in accordance with ASHRAE 90.1, the duct insulation shall be determined by Section 503.2.7, IECC 2006, as amended by the City of Tucson. Reference: Section 501.2, IECC 2006, as amended by the City of Tucson. 2. Provide calculations to show that ventilation for the kitchen addition complies with the requirements of footnote f, Table 403.3, IMC 2006. Reference: Section 403.3 IMC 2006 |
| 02/03/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/03/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/03/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/03/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 02/03/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 02/03/2009 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 02/03/2009 | RONALD BROWN | ZONING HC SITE | REVIEW | Approved | |
| 02/03/2009 | RONALD BROWN | ADA | REVIEW | Passed | |
| 02/11/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 02/11/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |