Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T09CM00251
Parcel: 128100540

Review Status: Active

Review Details: COMMERCIAL TI

Permit Number - T09CM00251
Review Name: COMMERCIAL TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2009 RONALD BROWN ADA REVIEW Passed NOT A COT PROJECT
02/03/2009 GERRY KOZIOL WWM REVIEW Passed
02/03/2009 DAVE MANN FIRE REVIEW Approved
02/04/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/10/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. MINIMUM 3/32" LETTERING IS REQUIRED ON ALL DRAWINGS UNLESS A WRITTEN APPEAL IS APPROVED BY THE BUILDING OFFICIAL, JESSIE SANDERS. THIS APPROVED APPEAL MUST ACCOMPANY DRAWINGS SUBMITTED FOR CHECKING.
2. SHEET G-004: SINCE THE EXISTING RESTROOMS ARE NOT IN THIS CONTRACT, THE MAJORITY OF THE DETAILS ON THIS SHEET CAN BE REMOVED.
3. SHEET I-201 NOTES: THE PARTITION PLAN LEGEND INDICATES NEW PARTITION TYPE A2 U.N.O., WHILE THE GENERAL PARTITION NOTES INDICATE NEW PARTITIONS TO BE TYPE A3 U.N.O. CLARIFY.
4. SHEET I-201; PARTITION D: PROVIDE DETAIL FOR PONY WALL CONNECTION TO EXISTING WALL TO RESIST LOADS PER IBC SECTION 1607.13.
5. SHEET I-901; TYPE A PARTITION DETAIL: PROVIDE THE LOCATION OF THE DETAIL AT THE TOP OF THE WALL. THE DETAIL SHOULD INDICATE CONNECTION SIZE/QUANTITY/SPACING TO RESIST LOADS PER IBC SECTION 1607.13.
02/10/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Denied 1. SEE BUILDING COMMENTS.
02/24/2009 ROBERT SHERRY WATER REVIEW Approved
02/24/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/24/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Detail 3/TH-3 shows the condensate from AC-1 being pumped to an existing gravity condensate drain. Show the size, location, and termination of the existing condensate drain along with the tonnage of the units currently connected to it. Reference: Section 307.2, IMC 2006.
2. Reprint the background for plan 1/TH-2 so it is legible. Reference: Section 106.3.1, IMC 2006.
02/26/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/27/2009 SUE REEVES REJECT SHELF RECEIVED