Permit Number: T09CM00249
Parcel: 13707045F

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM00249
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The range and recirculating exhaust hood (residential) were deleted from the community room (C-204) on the mechanical plans but have been retained on the architectural and electrical plans. If the range is desired, provide a Type I hood together with a make -up air system. Reference: Section 507.2.3, IMC 2006.
08/24/2009 ROBERT SHERRY WATER REVIEW Approved
08/24/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved. Provide a detail of the backflow preventer for yard water piping.
2. Comment not addressed. Provide a code schedule on the drawing cover sheet.