Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/24/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The range and recirculating exhaust hood (residential) were deleted from the community room (C-204) on the mechanical plans but have been retained on the architectural and electrical plans. If the range is desired, provide a Type I hood together with a make -up air system. Reference: Section 507.2.3, IMC 2006. |
08/24/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/24/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved. Provide a detail of the backflow preventer for yard water piping. 2. Comment not addressed. Provide a code schedule on the drawing cover sheet. |