Permit Number: T09CM00249
Parcel: 13707045F

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM00249
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2009 GERRY KOZIOL WWM REVIEW Approved
06/22/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 1: REVIEW SHEETS S1.2 AND S1.3 FOR 3/32" MINIMUM LETTERING.
2. PREVIOUS COMMENT 2: THE REFERENCE ON DETAILS 1, 2, AND 3 (SHEET A8.1) TO 22/S3.1 IS INCORRECT.
06/29/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1. On Utility Site Plan, include size and location of backflow preventer for yardwater piping. Include a detail. 2. Provide a code schedule on the cover sheet.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/07/2009 DELMA ROBEY OUT TO CUSTOMER Completed
07/07/2009 SUE REEVES REJECT SHELF Completed