Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM00249
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/17/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
06/22/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT 1: REVIEW SHEETS S1.2 AND S1.3 FOR 3/32" MINIMUM LETTERING. 2. PREVIOUS COMMENT 2: THE REFERENCE ON DETAILS 1, 2, AND 3 (SHEET A8.1) TO 22/S3.1 IS INCORRECT. |
06/29/2009 | RICK MYERS | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. On Utility Site Plan, include size and location of backflow preventer for yardwater piping. Include a detail. 2. Provide a code schedule on the cover sheet. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/07/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
07/07/2009 | SUE REEVES | REJECT SHELF | Completed |