Permit Number: T09CM00249
Parcel: 13707045F

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM00249
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2009 DAVE MANN FIRE REVIEW Approved
04/23/2009 GERRY KOZIOL WWM REVIEW Denied 1:CASA DEL PUEBLO II-S07-121 38 APT UNITS
2:CONNECTING TO EXSISTING ON-SITE PRIVATE SEWER
3:NEED IWC REVIEW & APPROVAL OF ELEVATOR SUMP DRAIN INDIRECT TO FS WITHOUT OIL/SAND SEPARATOR- TOM TOMCHAK- 443-6200
4:NEED WASTEWATER REVIEW OF LOCATION OF CONNECTION THROUGH ADJACENT PROPERTY WITH PRIVATE UTILITY EASEMENT- PCRWRD 3RD FLOOR ILENE DECKARD -740-6544
5:NEED TO PERMIT 6" ON-SITE PRIVATE SEWER-NEED COPY OF PLAN FOR 8TH FLOOR BASE MAP UPDATE- NEED DEQ REVIEW & APPROVAL OF ON-SITE PRIVATE SEWER- 740-3340
04/27/2009 JASON GREEN ENGINEERING REVIEW Approved Building only
04/30/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 1: REVIEW ALL SHEETS FOR 3/32" MINIMUM LETTERING (INCLUDING SHEETS S1.1B, S1.2, S1.3, ETC.). MINIMUM LETTERING REQUIREMENTS APPLY TO ALL DISCIPLINES, ALL SHEETS.
2. SHEET A8.1; DETAILS 1,2, AND 3: CLARIFY NOTE REFERENCE TO 22/S3.1.
3. PREVIOUS COMMENT 11: THE ROOF FRAMING KEY PLAN IN THE CALCULATIONS (3.1.1) AND THE FLOOR FRAMING KEY PLAN (4.1) NO LONGER MATCH THE DRAWING PLANS (ON S2.3 AND S2.4). MANY BEAM AND JOIST DESIGN REFERENCES HAVE BEEN OMITTED. CLARIFY AND PROVIDE CALCULATION KEY PLANS THAT MATCH THE BUILDING DRAWING PLANS.
04/30/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
05/06/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1. Provide site plan showing routing and size of building sewer.
2. Provide site plan showing routing, size, and location of backflow preventer, and yard water piping.
3. Provide material types for all piping, to be included in plumbing notes.
4. Provide cover sheet with code schedules.
5. Detail 10 P3.1: all fast closing valves require hammer arrestors. 609.10 2006 UPC.
6. Detail 2 P3.1: sump pump discharge requires swing check valve and gate valve. 710.4 2006 UPC.
7. Revise the size of the common drainage piping for the clothes washers (detail 2/P3.2) to comply with the requirements of footnote 5, Table 7-3, UPC 2006.
8. Given the temperature range of the water supply in Tucson (as high as 90.3 degrees Fahrenheit), specify how the instantaneous water heaters (IWH-1,2) that deliver a 57 degree Fahrenheit rise to the lavatory faucets can guarantee a maximum delivery temperature of 110 degrees Fahrenheit. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
9. Provide 0.5” of insulation with a maximum conductivity of 0.27 BTU per inch/h °F on the first 8 feet of supply and discharge piping for WH-1 and WH-2. Reference: Section 504.5, IECC 2006.
05/11/2009 ROBERT SHERRY WATER REVIEW Approved
05/11/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/21/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/17/2009 GERARDO BONILLA OUT TO CUSTOMER Completed
06/17/2009 SUE REEVES REJECT SHELF Completed