Permit Number: T09CM00229
Parcel: 12902091D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM00229
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/29/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
01/30/2009 STEVE SHIELDS ZONING REVIEW Approved
01/30/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/30/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied 190 S STRATFORD , #160 , T09CM00229


DENIED , THE NEC 2005 230 , ALLOWS ONLY ONE SERVICE TO UNIT # 160 , THERE ARE TWO PROVIDED IN ONE , PROVIDE INFORMATION ON THIS PLEASE.



RAY MAJUTA
ELECTRICAL PLAN CK
1/30/09
01/30/2009 ROBERT SHERRY WATER REVIEW Approved
01/30/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
01/30/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the water riser diagrams to show the two water sources.
2. Provide riser diagrams for the waste and vent piping.
3. Clarify the scheduled expansion tank; is it part of the current project? Are the existing water heaters being replaced?
01/30/2009 RONALD BROWN ZONING HC SITE REVIEW Approved 1. COUNTER TOP IN BREAK ROOM TO BE CHANGED TO 2'-10".
01/30/2009 RONALD BROWN ADA REVIEW Passed
02/05/2009 GERRY KOZIOL WWM REVIEW Approved
02/05/2009 CPIERCE1 FIRE REVIEW Needs Review
02/05/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review