Permit Number: T09CM00207
Parcel: 11942009F

Review Status: Completed

Review Details: OTHER

Permit Number - T09CM00207
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/29/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. This activity is being reviewed to the 2006 UPC. If the 2006 IPC is desired, submit an appeal to the building official.
2. Comment not addressed. The minimum residual water pressure is 15 PSI, not 8 PSI. Reference: Section 608.1, UPC 2006.
3. Comment not addressed. Provide an upper terminal cleanout for the break room sink. Reference: Section 707.4, UPC 2006.
12/29/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the size of the condensate drains in accordance with Section 307.2.1, IMC 2006, as amended by the City of Tucson (i.e. combining 2 units of any size requires a minimum 1" condensate drain).

Final Status

Task End Date Reviewer's Name Type of Review Description
01/12/2010 SUE REEVES OUT TO CUSTOMER Completed
01/12/2010 SUE REEVES REJECT SHELF Completed